MindMap Gallery Architectural structure and selection mind map
A mind map about building structure and type selection, including simplified structural design, complex high-rise building structural design, etc.
Edited at 2023-11-20 16:49:51This is a mind map about bacteria, and its main contents include: overview, morphology, types, structure, reproduction, distribution, application, and expansion. The summary is comprehensive and meticulous, suitable as review materials.
This is a mind map about plant asexual reproduction, and its main contents include: concept, spore reproduction, vegetative reproduction, tissue culture, and buds. The summary is comprehensive and meticulous, suitable as review materials.
This is a mind map about the reproductive development of animals, and its main contents include: insects, frogs, birds, sexual reproduction, and asexual reproduction. The summary is comprehensive and meticulous, suitable as review materials.
This is a mind map about bacteria, and its main contents include: overview, morphology, types, structure, reproduction, distribution, application, and expansion. The summary is comprehensive and meticulous, suitable as review materials.
This is a mind map about plant asexual reproduction, and its main contents include: concept, spore reproduction, vegetative reproduction, tissue culture, and buds. The summary is comprehensive and meticulous, suitable as review materials.
This is a mind map about the reproductive development of animals, and its main contents include: insects, frogs, birds, sexual reproduction, and asexual reproduction. The summary is comprehensive and meticulous, suitable as review materials.
Structure and selection
Hybrid structural design
General provisions
The applicable maximum height for mixed structure high-rise buildings should comply with the requirements in Table 11.1.2.
The height-to-width ratio of mixed-structure high-rise buildings should not be greater than the requirements in Table 11.1.3.
For hybrid structures under wind load and earthquake action, the ratio Δu/h of the maximum interstory displacement calculated by the elastic method to the story height should not exceed the requirements in Table 11.1.4.
During seismic design, the seismic shear force borne by the frame columns on each floor of the steel frame-reinforced concrete cylinder structure shall not be less than the smaller of 25% of the total shear force at the bottom of the structure and 1.8 times the maximum seismic shear force of the frame part. ; The seismic shear force borne by the frame columns on each floor of the steel concrete frame-reinforced concrete cylinder shall comply with the provisions of Article 8.1.4 of this regulation.
Structural layout and structural design
The floor plan of the hybrid structure shall comply with the following provisions:
The shape of the building plane should be simple and regular, and regular and symmetrical planes such as square and rectangular should be used, and the lateral force-resisting center of the structure should coincide with the horizontal resultant force center as much as possible. The bays and depth of the building should be unified.
In the tube-in-tube structural system, when the peripheral steel frame columns adopt H-shaped cross-section columns, the strong axis direction of the column section should be arranged in the plane of the peripheral cylinder; the corner columns should adopt cross-shaped, square or circular cross-sections;
The main beams of the floor should not rest on the connecting beams of the core tube or inner tube.
The vertical layout of the hybrid structure should meet the following requirements:
The lateral stiffness and bearing capacity of the structure should change evenly along the vertical direction, and the component cross-section should gradually decrease from bottom to top without sudden changes;
When the upper and lower parts of the frame columns are of different types and materials, a transition layer should be set;
Reliable transition strengthening measures should be taken for floors with sudden changes in stiffness, such as transfer floors, reinforced floors, open top floors, top protrusions, the interface between steel concrete frames and steel frames, and adjacent floors;
When supporting the steel frame part, eccentric supports and energy-dissipating supports should be used. The supports should be arranged continuously, and should be arranged in two mutually perpendicular directions and interconnected with each other; the support frame is in the underground part and should be extended to the foundation.
For high-rise buildings with a mixed structure system, when the seismic fortification level is 7 degrees and the house height is no more than 130m, it is appropriate to install shaped steel columns at the intersection of the floor steel beams or shaped steel concrete beams and the reinforced concrete cylinder and at the four corners of the cylinder; When the height is greater than 130m and the seismic fortification level is 8 or 9, profiled steel columns should be installed at the intersection of the floor steel beams or profiled steel concrete beams and the reinforced concrete cylinder and at the four corners of the cylinder.
For high-rise buildings with mixed structural systems, the reinforced concrete cylinder should bear the main horizontal force, and effective measures should be taken to ensure the ductility of the reinforced concrete cylinder.
In the hybrid structure, the beams and columns in the plane of the peripheral frame should be rigidly connected; the connections between the floor beams, the reinforced concrete cylinder and the peripheral frame columns can be rigidly connected or hinged.
In steel frame-reinforced concrete cylinder structures, when H-shaped cross-section columns are used, the strong axis direction of the column section should be arranged in the plane of the peripheral frame; the corner columns should be square, cross-shaped or circular in cross-section.
In hybrid structures, outrigger truss reinforcement layers can be used, and peripheral trusses can be arranged at the same time if necessary. The plane of the outrigger truss should coincide with the center line of the lateral force-resistant wall. The outrigger trusses should be rigidly connected to the lateral force-resistant wall and should extend into and penetrate the lateral force-resistant wall. The connection between the outrigger trusses and the peripheral frame columns should be hinged or semi-rigid.
When an outrigger truss reinforcement layer is arranged, effective measures should be taken to reduce the change in the internal force of the truss rods caused by the difference in vertical deformation of the outer columns and the concrete cylinder.
The floor should use profiled steel plate cast-in-place concrete composite floor, cast-in-place concrete floor or prestressed composite floor. The floor and steel beams should be reliably connected.
For buildings with large openings on the floor or for conversion floors, cast-in-place floor slabs should be used. For parts with large floor openings, it is advisable to use procedures that consider floor deformation to calculate internal forces and displacements, or to take strengthening measures such as setting up rigid horizontal supports.
When calculating the internal force and displacement in the elastic stage, the steel cross-section can be used to calculate steel beams and columns, and the stiffness of steel concrete components can be calculated using the sum of the stiffness of the steel part and the stiffness of the reinforced concrete part.
When performing structural elasticity analysis, the joint effect of steel beams and concrete floors should be considered. The stiffness of the beam can be 1.5 to 2.0 times that of the steel beam, but a reliable connection between the steel beam and the floor should be ensured.
In the calculation of internal forces and displacements, the deformation of the floor slab in the plane should be considered for floors with outrigger trusses.
When calculating the vertical load effect, the influence of the difference in axial deformation of columns and walls during the construction process should be considered, and the adverse effects of the internal forces on the steel beams and columns due to the creep shrinkage of the reinforced concrete cylinder under long-term load should be considered.
When the reinforced concrete cylinder is constructed before the steel frame, the unfavorable stress state of the reinforced concrete cylinder under the action of wind and other loads during the construction stage should be considered. The steel frame components should be checked and calculated before the concrete is poured. Bearing capacity, stability and displacement under wind load, and determine the number of intervals between steel frame installation and concrete floors based on this.
The connection between the two ends of the steel support between columns and the column or reinforced concrete cylinder can be calculated as a hinge.
The damping ratio of the hybrid structure under frequent earthquakes can be taken as 0.04.
In the seismic design of steel-concrete hybrid structure houses, the seismic resistance levels of the reinforced concrete cylinder and profiled steel concrete frame should be determined according to Table 11.2.19, and should comply with the corresponding calculation and structural measures.
The steel components in the steel-concrete hybrid structure should be designed in accordance with the current national standards "Steel Structure Design Code" GB 50017 and "Technical Specifications for Steel Structures in High-Rise Civil Buildings" JGJ 99; the reinforced concrete components should be designed in accordance with the current national standard "Concrete Design Code" The design shall be carried out in accordance with the relevant provisions of GB 50010 and Chapter 7 of this Regulation; the section design of shaped steel concrete members may be carried out in accordance with the current industry standard "Technical Regulations for Shaped Steel Concrete Composite Structures" JGJ 138.
When there is a combination of seismic action, the seismic adjustment coefficient γRE of the bearing capacity of shaped steel concrete members and steel members should be selected according to Tables 11.2.21-1 and 11.2.21-2.
Among steel concrete members, when the width-to-thickness ratio of the steel plate meets the requirements of Table 11.2.22, local stability verification does not need to be performed (Figure 11.2.22)
Complex high-rise building structural design
General provisions
Structures with transfer layers, structures with reinforced layers, staggered-level structures and conjoined structures should not be used in 9-degree seismic design.
In 7-degree and 8-degree seismic design, the heights of split-level high-rise buildings with shear wall structures should not be greater than 80m and 60m respectively; the heights of split-level high-rise buildings with frame-shear wall structures should not be greater than 80m and 60m respectively. In seismic design, it is not suitable to use conjoined structures for Class B high-rise buildings; for Class B high-rise buildings with a tube-in-tube structure with a transition layer at the bottom, when a wall frame composed of shear walls is used above the outer tube frame support layer, the maximum The applicable height should be appropriately lower than the value specified in Table 4.2.2-2 of this regulation.
For complex stress-bearing parts of complex high-rise building structures, stress analysis should be carried out, and reinforcement design and verification should be carried out according to stress.
The transfer floor shall adopt cast-in-place floor slabs, and its concrete strength grade shall not be lower than C30. The concrete strength grade of frame beams, frame pillars, box-shaped transfer structures and transfer slabs shall not be lower than C30.
High-rise building structure with transfer layer
At the bottom of the high-rise building structure, when some of the vertical components (shear walls, frame columns) of the upper floor cannot directly and continuously penetrate the ground, a structural transfer layer should be set up, and the transfer structural components should be arranged on the structural transfer layer. (This section stipulates the design of shear wall structures with support wall transfer layers (partially frame-supported shear wall structures) and cylinder structures with support column transfer layers.) The transfer structure components can be beams, trusses, and open-web trusses. , box structure, diagonal brace, etc.; thick plates can be used as conversion components in non-seismic design and 6-degree seismic design, and thick plates can be used in basements with 7 and 8-degree seismic design.
The number of floors of the large space above the ground for partially frame-supported shear wall high-rise building structures at the bottom should not exceed 3 floors at 8 degrees, 5 floors at 7 degrees, and the number of floors can be appropriately increased at 6 degrees; the bottom belt conversion The layer's frame-core tube structure and the outer tube are tube-in-tube structures of dense column frames, and the position of the conversion layer can be appropriately increased.
The layout of high-rise building structures with transfer floors at the bottom shall comply with the following requirements:
The floor-to-ceiling shear wall and the bottom wall of the cylinder should be thickened;
The lateral stiffness ratio between the upper structure and the lower structure of the transfer layer shall comply with the provisions of Appendix E of this regulation;
Floor slabs around the frame support layer should not be arranged at staggered levels;
The openings of floor-to-ceiling shear walls and cylinders should be arranged in the middle of the wall;
It is not appropriate to set up side door openings in the wall on the first floor above the frame-supported shear wall transfer beam, nor to set up door openings above the center column;
The spacing l of floor-to-ceiling shear walls in long rectangular plan buildings should comply with the following regulations:
Non-seismic design: l≤3B and l≤36m;
Earthquake-resistant design: When the bottom is the 1st to 2nd floor frame support layer:
And l≤2B and l≤24m When the bottom is a frame support layer with 3 or more floors:
l≤1.5B and l≤20m where B——floor width.
The distance between the floor-to-ceiling shear wall and the adjacent frame support should not be greater than 12m when the frame supports the 1st or 2nd floor, and should not exceed 10m when the frame supports the 3rd floor or above.
For a high-rise building structure with a transfer layer at the bottom, the height of the reinforced part at the bottom of the shear wall can be taken as the larger value of the frame support layer plus the height of the two floors above the frame support layer and 1/8 of the total height of the wall legs.
The seismic resistance grade of high-rise building structures with transfer floors at the bottom shall comply with the provisions of Section 4.8 of this regulation. For some frame-supported shear wall structures, when the transfer layer is set on the 3rd floor or above, the seismic resistance levels of the frame pillars and the reinforced parts at the bottom of the shear wall should still be in accordance with Tables 4.8.2 and 4.8 of this regulation. The provisions of 3 will be adopted by raising one level. If it is already a special level, it will not be raised any more.
For high-rise building structures with transfer floors, the seismic shear force of the weak layer should be multiplied by an increase factor of 1.15 in accordance with Article 5.1.14 of this regulation. The internal forces calculated for the horizontal seismic effects of special first-, first-, and second-level conversion members should be multiplied by the increase coefficients 1.8, 1.5, and 1.25 respectively; in the 8-degree seismic design, the effects of vertical earthquakes should also be considered for the conversion members.
For high-rise building structures with transfer floors, the standard values of seismic shear force borne by frame pillars shall be adopted in accordance with the following provisions:
When the number of frame pillars per floor is no more than 10, when the frame support layer is 1 to 2 stories, the shear force on each column should be at least 2% of the base shear force; when the frame support layer is 3 stories and above 3 stories, the shear force on each column should be at least 3% of the base shear force;
When the number of frame pillars per layer is more than 10, when the frame support layer is 1 to 2 stories, the sum of the shear force of each frame pillar should be taken as 20% of the base shear force; when the frame support layer is 3 stories and When there are more than 3 floors, the sum of the shear forces of the frame pillars on each floor should be 30% of the base shear force.
After the shear force of the frame pillar is adjusted, the bending moment of the frame pillar and the shear force and bending moment of the column end beam (excluding the conversion beam) should be adjusted accordingly. The axial force of the frame pillar does not need to be adjusted.
The design of frame support beams should meet the following requirements:
The minimum reinforcement ratio of the upper and lower longitudinal steel bars of the beam should not be less than 0.30% respectively in non-seismic design; in seismic design, the special first, first and second grade should not be less than 0.60%, 0.50% and 0.40% respectively;
For a frame-supported beam under eccentric tension, at least 50% of the upper longitudinal steel bars of the support should run through the entire length of the beam, and all the lower longitudinal steel bars should pass straight into the column; waist bars with a spacing of no more than 200mm and a diameter of no less than 16mm should be configured along the beam height;
The stirrups at the frame support beam support (within the height of the beam section 1.5 from the column edge) should be dense. The diameter of the stirrups in the dense area should not be less than 10mm, and the spacing should not be greater than 100mm. The minimum area stirrup ratio in the densification area shall not be less than 0.9ft/fyv in non-seismic design; in seismic design, the special first, first and second grade shall not be less than 1.3ft/fyv, 1.2ft/fyv and 1.1ft/ respectively. fyv.
The design of frame support beams should also meet the following requirements:
The center lines of the frame support beams and frame support sections should coincide;
The cross-sectional width of the frame-supported beam should not be greater than the cross-sectional width of the frame support in the corresponding direction, and should not be less than twice the cross-sectional thickness of the wall above it, and should not be less than 400mm; when supporting columns on the beam, it should not be less than the column cross-section width in the beam width direction. . The height of the beam section should not be less than 1/6 of the calculated span in seismic design, and should not be less than 1/8 of the calculated span in non-seismic design; frame-supported beams can use haunched beams;
The maximum shear design value of the frame-supported beam section combination should meet the following requirements:
When the wall above the frame support beam has a door opening or a support column on the beam, the stirrups of the frame support beam in this part should be densely arranged, and the stirrup diameter, spacing and stirrup ratio should not be lower than Article 10.2.8 of this regulation According to the provisions of paragraph 3; when the opening is close to the end of the frame-supported beam and the shear bearing capacity of the beam does not meet the requirements, measures such as adding haunches to the frame-supported beam or increasing the stiffness of the connecting beams at the frame-supported wall opening can be taken;
The longitudinal steel bar joints of beams should be mechanically connected. The cross-sectional area of the joint steel bars in the same section should not exceed 50% of the cross-sectional area of all longitudinal bars. The joint location should avoid the openings in the upper wall, the supporting columns on the beams, and the areas with greater stress. parts;
The anchorage of the upper and lower longitudinal steel bars and waist bars of the beam should comply with the requirements of Figure 10.2.9; when the upper part of the beam is equipped with multiple rows of longitudinal steel bars, the length of the inner row of steel bars anchored into the column can be appropriately reduced, but should not be shorter than the steel bars Anchorage length 1a (non-seismic design) or 1aE (seismic design);
It is not suitable to make holes in frame support beams. If a hole is needed, the hole should be located away from the edge of the frame pillar. The upper and lower chords should be reinforced with shear reinforcement. The hole should be equipped with reinforced steel bars or reinforced with section steel. The section weakened by the hole should be calculated for bearing capacity.
The vertical lateral force-resistant components (walls, columns) on the upper part of the transfer layer should fall directly on the main structure of the transfer layer. When the vertical layout of the structure is complex, and the frame-supported main beam supports the shear wall and supports the conversion secondary beam and its upper shear wall, stress analysis should be carried out, the reinforcement should be checked according to the stress, and reinforcement structural measures should be strengthened. The structural transfer layer of high-rise buildings with B-level frame-supported shear walls should not adopt the frame-supported primary and secondary beam scheme.
The frame support design should meet the following requirements:
The reinforcement ratio of all longitudinal steel bars in the column shall comply with the provisions of Article 6.4.3 of this regulation;
During seismic design, the stirrups of the frame pillars should be composite spiral hoops or tic-shaped composite hoops. The stirrup diameter should not be less than 10mm, and the stirrup spacing should not be greater than the smaller of 100mm and 6 times the diameter of the longitudinal steel bars, and should be installed along the full height of the column. encryption;
During seismic design, the characteristic value of the stirrup configuration in the primary and secondary column density areas should be increased by 0.02 from the value specified in Table 6.4.7 of this regulation, and the volume stirrup ratio of the column stirrups should not be less than 1.5%.
The design of frame pillars should also meet the following requirements:
The combined maximum shear design value of the frame support section should meet the following requirements:
The width of the column section should not be less than 400mm in non-seismic design, and should not be less than 450mm in seismic design; the column section height should not be less than 1/15 of the frame support beam span in non-seismic design, and should not be less than 1/15 of the frame support beam span in seismic design. /12;
The combined bending moment values of the upper end of the first and second level columns connected to the conversion members and the lower end of the column on the ground floor should be multiplied by the increase coefficients 1.5 and 1.25 respectively. The design values of the bending moments at the column ends of other floor frame pillars should comply with Article 6.2 of this regulation. The provisions of Article 1;
1. The design value of the shear force of the secondary column end section shall comply with the provisions of Article 6.2.3 of this regulation;
The design values of bending moment and shear force of frame-supported corner columns shall be multiplied by an increase factor of 1.1 on the basis of paragraphs 3 and 4 of this article respectively;
The axial force generated by the earthquake action on the primary and secondary frame pillars should be multiplied by the increase factors 1.5 and 1.2 respectively, but this increase factor should not be considered when calculating the column axial pressure ratio;
The spacing between longitudinal steel bars should not be greater than 200mm in seismic design; it should not be greater than 250mm in non-seismic design, and should not be less than 80mm. During seismic design, the reinforcement ratio of all longitudinal steel bars in the column should not be greater than 4.0%;
The longitudinal steel bars of the frame pillars within the upper wall should extend into the upper wall for no less than one layer, and the remaining column bars should be anchored into the beams or slabs. The length of the steel bars anchored into the beam shall not be less than 1aE (seismic design) or 1a (non-seismic design) from the column edge;
In non-seismic design, the frame pillars should use composite spiral hoops or tic-shaped composite hoops. The stirrup volume ratio should not be less than 0.8%, the stirrup diameter should not be less than 10mm, and the stirrup spacing should not be greater than 150mm.
The structure of the upper wall of the frame support beam should meet the following requirements:
When there is a side door opening in the wall above the frame support beam, the wall beside the opening should be equipped with flange walls, end columns or thickened (Figure 10.2.13), and the edge components should be restrained in accordance with Article 7.2.16 of this regulation. Reinforcement design is required;
The anchoring length of the vertical steel bars of the wall on the frame support beam in the transfer beam should not be less than laE in seismic design, and should not be less than la in non-seismic design;
The reinforcement of the wall on the first floor above the frame support beam should be calculated according to the following formula:
The horizontal construction joint between the transfer beam and its upper wall should be checked for slip resistance in accordance with Article 7.2.13 of this regulation.
The bending moment design value of the reinforced part at the bottom of the special first-, first- and second-level floor-to-ceiling shear walls should be adopted based on the bending moment value of the wall bottom section with seismic action multiplied by the increase coefficient 1.8, 1.5, 1.25; the shear design value should be According to the provisions of Article 7.2.10 of this regulation, the shear force increase coefficient of the special grade should be 1.9. Wall limbs of floor-to-ceiling shear walls should not be subjected to eccentric tension.
For partially frame-supported shear wall structures, the minimum reinforcement ratio of horizontal and vertical distributed steel bars at the bottom reinforcement part of the shear wall should not be less than 0.3% in seismic design, and should not be less than 0.25% in non-seismic design; The spacing between steel bars should not be greater than 200mm, and the diameter of the steel bars should not be less than 8mm.
For the reinforced bottom part of the shear wall of a frame-supported shear wall structure, wing walls or end columns should be set up at both ends of the wall. In seismic design fashion, restraining edge members should be set up in accordance with Article 7.2.16 of this regulation.
The floor-to-ceiling shear wall foundation should have good integrity and anti-rotation capabilities.
The cross-sectional shear design value of the rectangular plane building frame supporting floor slab designed for earthquake resistance shall meet the following requirements:
For a rectangular plane building frame supporting floor slab designed for earthquake resistance, when the plane is long or irregular and the internal forces of each shear wall differ greatly, a simplified method can be used to check the bending capacity of the floor slab plane.
The thickness of the transfer floor slab should not be less than 180mm, it should be double-layered and bi-directionally reinforced, and the reinforcement rate in each direction of each floor should not be less than 0.25%. The steel bars in the floor slab should be anchored in the side beams or inside the wall; floor-to-ceiling shear walls and around the outside of the cylinder It is not advisable to make holes in the floor slab. Edge beams should be installed at the edges of floor slabs and around larger openings. Their width should not be less than twice the thickness of the slab. The reinforcement rate of longitudinal steel bars should not be less than 1.0%. The steel bar joints should be mechanically connected or welded. Floor slabs on floors adjacent to the transfer floor should also be appropriately strengthened.
The thickness of the upper and lower floors of the box-shaped conversion structure should not be less than 180mm. In addition to bending moment calculations, the influence of tension and pressure in its own plane should also be considered when reinforcing the plate.
Thick plate design should meet the following requirements:
The thickness of the converted thick plate can be determined by calculation of bending resistance, shear resistance and punching resistance;
The thick plate can be converted into a partial thin plate, and the junction between the thin plate and the thick plate can be added with a haunch; the thick plate can also be partly made into a sandwich plate;
The converted thick plate should be designed in section according to the design values of shear force and bending moment of the main cross-beam system divided in the overall calculation, and the reinforcement should be checked according to the analysis results of the finite element method. Bending longitudinal steel bars can be arranged in two directions along the double layer and lower part of the transfer plate. The total reinforcement ratio in each direction should not be less than 0.6%. The area reinforcement ratio of the concealed beam shear stirrups in the transfer plate should not be less than 0.45%;
In order to prevent lamellar horizontal cracks along the thickness direction at the ends of the converted thick plates, it is advisable to configure a steel skeleton mesh around the outer periphery of the thick plates for reinforcement;
The longitudinal steel bars of the shear walls and columns at the upper and lower parts of the transfer slab should be reliably anchored within the transfer slab.
The floor slabs on the conversion thick slab and the next floor should be appropriately strengthened, and the thickness of the floor slab should not be less than 150mm.
When the upper dense columns of frame-core tube structures and tube-in-tube structures are converted into lower sparse columns, conversion beams or conversion trusses can be used. The conversion trusses should be set up on the full floor, and the intersection of the diagonal rods should be used as the fulcrum of the upper dense columns. The nodes of the transfer truss should be strengthened with reinforcement and structural measures to prevent the adverse effects caused by stress concentration.
When using a Vierendeel truss transfer layer, the Vierendeel truss should be set up on the full floor, and it should have sufficient stiffness to ensure its overall stress. The upper and lower chords of the open-web truss should consider the floor function. The vertical web bars should be reinforced according to strong shear and weak bending, strengthen the stirrup configuration, and strengthen the connection structure with the upper and lower chords. Vierendeel trusses should strengthen the anchoring connection structure between the upper and lower chords and frame columns.
High-rise building structure with reinforced layer
When the lateral stiffness of the frame-core structure cannot meet the design requirements, the space of the building's refuge floor and equipment floor can be used vertically to set up horizontal outriggers with appropriate stiffness to form a high-rise building structure with a reinforced layer. If necessary, peripheral horizontal annular belt members can also be provided. The horizontal outrigger members and peripheral ring members used in the reinforced layer can be in the form of oblique web rod trusses, solid beams, box beams for the entire floor or across several floors, and hollow trusses.
The structural design of high-rise buildings with reinforced layers should meet the following requirements:
The location and number of reinforcement layers must be reasonable and effective. When arranging one reinforcement layer, the location can be near 0.6 times the height of the house; when arranging two reinforcement layers, the location can be near the top floor and 0.5 times the height of the house; when arranging multiple reinforcement layers When layering, the reinforcing layer should be evenly arranged vertically from the top layer downward;
The horizontal outrigger components of the reinforced layer should penetrate the core tube, and their plan layout should be located at the corners and T-points of the core tube; the connection between the horizontal outrigger components and the surrounding frame should be hinged or semi-rigid. In the calculation of structural internal forces and displacements, the deformation in the floor plane should be considered for floors with horizontal outrigger trusses;
Damage caused by increased internal forces of the reinforced layer and its adjacent layer frame columns should be avoided. The reinforcement structure of the reinforced layer and its upper and lower frame columns should be strengthened; the reinforcement of the core tube of the reinforced layer and its adjacent layers should be strengthened;
The stiffness and reinforcement of the reinforced layer and its adjacent floors should be strengthened;
Measures should be taken in the construction procedures and connection structures to reduce the impact of vertical temperature deformation and axial compression of the structure on the reinforcement layer.
During seismic design, high-rise building structures with reinforced layers should meet the following structural requirements:
The seismic resistance grade of the frame columns and core tube shear walls of the reinforced layer and its adjacent layers should be raised by one level, and the first level should be raised to the special first grade. If the original seismic grade is the special first grade, it will not be improved;
The stirrups of the reinforced layer and the frame columns of the adjacent floors above and below should be densely packed throughout the column section, and the axial compression ratio limit should be reduced by 0.05 from the value specified in Table 6.4.2 of this regulation.
Split level structure
In seismic design, high-rise buildings should avoid staggered levels in the vertical direction. When different parts of the house have staggered floors due to different functions, anti-seismic joints should be used to divide them into independent structural units.
Structural systems with similar structural layout and lateral stiffness should be used on both sides of the staggered floor.
In a split-level structure, the staggered floors should each participate in the overall calculation of the structure and should not be combined into one floor calculation.
The cross-sectional height of frame columns at staggered levels should not be less than 600mm, the concrete strength grade should not be lower than C30, the seismic resistance grade should be improved by one level, and the stirrups should be densely packed throughout the column section.
For shear walls with out-of-plane stress at staggered levels, the cross-sectional thickness should not be less than 200mm in non-seismic design, and should not be less than 250mm in seismic design, and vertical wall limbs or buttresses should be installed; seismic grade It should be adopted at a higher level. The concrete strength grade of the staggered shear wall should not be lower than C30, and the reinforcement ratio of horizontal and vertical distributed steel bars should not be less than 0.3% in non-seismic design and not less than 0.5% in seismic design.
Siamese structure
Each independent part of the conjoined structure should have the same or similar body shape, plane and stiffness. A biaxially symmetric planar form should be adopted. In 7-degree and 8-degree seismic design, buildings with vastly different layers and stiffnesses should not adopt conjoined structures.
When designing for 8-degree seismic resistance, the impact of vertical earthquakes should be considered on the connectors of the conjoined structure.
Connector structure and main structure
The connector structure and the main structure should be rigidly connected. If necessary, the connector structure can be extended to the inner cylinder of the main part and reliably connected to the inner cylinder.
When the connector structure is non-rigidly connected to the main structure, the bearing slippage should be able to meet the displacement requirements in both directions under rare earthquakes.
Connector structure
The connector structure should strengthen structural measures. The side beam cross-section of the connector structure should be enlarged. The thickness of the floor slab should not be less than 150mm. Double-layer two-way steel mesh should be used. The reinforcement ratio of each layer of steel mesh in each direction should not be less than 0.25%.
The connector structure can be equipped with steel beams, steel trusses and profiled steel concrete beams. The profiled steel should extend into the main structure and strengthen the anchorage.
When the connecting structure contains multiple floors, the design and construction of the bottom one to two floors should be particularly strengthened.
During seismic design, the seismic resistance grade of the connector and the structural members adjacent to the connector should be raised by one level, and the first level should be raised to the special first grade. If the original seismic grade is the special first grade, it will not be improved.
multi-tower structure
The number of floors, planes and stiffness of each tower in a multi-tower building structure should be close; the towers should be arranged symmetrically with respect to the chassis. The distance between the center of mass of the tower structure and the chassis structure should not be greater than 20% of the corresponding side length of the chassis.
During seismic design, the transfer layer should not be placed in the upper tower of the chassis roof; otherwise, effective seismic measures should be taken.
The thickness of the chassis roof floor slab should not be less than 150mm, and the reinforcement structure should be strengthened; structural measures should also be strengthened for the floors on the upper and lower structures of the chassis roof. When the chassis roof is a structural transfer layer, it shall comply with the provisions of Article 10.2.20 of this regulation.
In seismic design, the roof beams of the podium connectors between multiple towers should be strengthened; the peripheral columns and shear walls in the towers connected to the podium connectors should be within the height range from the fixed end to the first floor of the podium roof. The minimum reinforcement ratio of longitudinal steel bars should be appropriately increased, the column stirrups should be densely packed throughout the upper and lower floors of the podium roof, and the shear walls should be equipped with restraining edge members in accordance with Article 7.2.16 of this regulation.
Barrel structure design
General provisions
The height of the tube-in-tube structure should not be less than 60m, and the aspect ratio should not be less than 3.
The concrete strength grade of the cylinder structure should not be lower than C30.
When columns on adjacent floors are not connected, components such as transfer beams should be installed. The height of the transfer beam should not be less than 1/6 of the span. The structural design with conversion components shall comply with the relevant provisions of Chapter 10 of this Regulation.
Double-layer two-way steel bars should be installed at the outer corners of the floor of the cylinder structure (Figure 9.1.5). The single-layer one-way reinforcement ratio should not be less than 0.3%, the diameter of the steel bars should not be less than 8mm, the spacing should not be greater than 150mm, and the reinforcement range should not be less than 0.3%. Less than 1/3 and 3m of the distance from the outer frame (or outer cylinder) to the outer wall of the inner cylinder.
When the middle distance between the outer wall of the core cylinder or inner cylinder and the outer frame column is greater than 12m for non-seismic design and greater than 10m for seismic design, measures such as setting up additional inner columns should be taken.
The cross-sectional shape of the shear wall in the core tube or inner cylinder should be simple; walls with complex cross-sectional shapes can be reinforced according to stress.
The reinforced parts of the cylinder wall, the arrangement of edge components and the design of reinforcements shall comply with the relevant provisions of Chapter 7 of these regulations. During seismic design, the core tube of the frame-core tube structure and the inner tube of the tube-in-tube structure shall be equipped with restraint edge members or structural edge members in accordance with the provisions of Articles 7.2.15 to 7.2.17 of this regulation, and the bottom reinforcement part shall be under the gravity The axial compression ratio of the wall under load should not exceed the requirements in Table 7.2.14 of this regulation. The corner edge components of the core tube of the frame-core tube structure should be strengthened according to the following requirements: the length of the restraining edge component at the bottom reinforcement along the wall pier should be 1/4 of the wall pier section height, and stirrups should be used throughout the range of the restraining edge component. ; The restraining edge components should be installed above the bottom reinforcement part in accordance with the provisions of Article 7.2.16 of this regulation.
The outer wall of the core tube or inner tube should not be continuously opened in the horizontal direction, and the cross-sectional height of the wall limbs between holes should not be less than 1.2m; when the ratio of the cross-sectional height and thickness of the wall limbs between holes is less than 3, the reinforcement design should comply with The relevant provisions of Article 7.2.5 of this Regulation.
In seismic design, the axial compression ratio limits of frame tube columns and frame columns can be based on the provisions of frame-shear wall structures.
The main beams of the floor should not rest on the connecting beams of the core tube or inner tube.
In addition to complying with the provisions of this chapter, the cross-sectional design and structural measures of various components of the cylinder structure shall also comply with Article 6 of this regulation.
Frame-Core Structure
The core tube should run through the entire height of the building. The width of the core tube should not be less than 1/12 of the total height of the tube. When the tube structure is equipped with corner tubes, shear walls or components that enhance the overall stiffness of the structure, the width of the core tube can be appropriately reduced.
The core tube should have good integrity and meet the following requirements:
Wall limbs should be arranged evenly and symmetrically;
It is not advisable to open holes near the corners of the cylinder. When unavoidable, the distance from the inner wall of the cylinder corner to the opening should not be less than 500mm and the cross-sectional thickness of the hole wall;
The cross-sectional thickness of the core tube outer wall should not be less than 1/20 and 200mm of the floor height. The bottom reinforcement part for the first and second level seismic design should not be less than 1/16 and 200mm of the floor height. If it is not satisfied, the thickness should be determined according to the appendix of this regulation. D Calculate the stability of the wall, and add buttress columns or buttress walls if necessary; when meeting the bearing capacity requirements and the axial pressure ratio limit (only for earthquake resistance design), the inner wall of the core tube can be appropriately thinned, but it should not be smaller than 160mm;
The horizontal and vertical reinforcement of the cylinder wall should not be less than two rows
During seismic design, the ductility of the coupling beams of the core tube should be improved by configuring cross-concealed bracing, setting up horizontal joints, or reducing the height-to-width ratio of the beam section.
During seismic design, the seismic shear force of frame columns at each floor should be adjusted with reference to the provisions of Article 8.1.4 of this regulation.
Frame beams must be provided between the perimeter columns of frame-core structures.
The shear section of the core tube connecting beam shall comply with the requirements of Article 9.3.6 of this Regulation, and its structural design shall comply with the provisions of Articles 9.3.7 to 9.3.8 of this Regulation.
Tube-in-tube structure
The planar shape of the tube-in-tube structure should be round, regular polygon, oval or rectangular, and the inner tube should be centered.
The aspect ratio of a rectangular plane should not be greater than 2.
The side length of the inner cylinder can be 1/12 to 1/15 of the height. If there is another corner cylinder or shear wall, the plane size of the inner cylinder can be appropriately reduced. The inner tube should run through the entire height of the building, and the vertical stiffness should change evenly.
The angles of the triangular plane should be cut. The length of the cut corners of the outer cylinder should not be less than 1/8 of the corresponding side length. A corner post or cylinder with greater stiffness can be set at the corner. The length of the cut corners of the inner cylinder should not be less than 1/10 of the corresponding side length. , the cylinder wall at the cut corner should be appropriately thickened.
The outer frame tube shall comply with the following requirements:
The distance between columns should not be greater than 4m. The long side of the section of the frame column should be arranged along the direction of the column wall. If necessary, a T-shaped section can be used;
The area of the opening should not be greater than 60% of the wall area, and the height-to-width ratio of the opening should be similar to the ratio of floor height to column spacing;
The cross-sectional height of the outer frame tube beam can be taken as 1/4 of the column clear distance;
The cross-sectional area of the corner columns can be 1 to 2 times that of the center column.
The cross-sectional dimensions of the outer frame tube beam and inner tube connecting beam should meet the following requirements:
The structural reinforcement of outer frame tube beams and inner tube connecting beams should meet the following requirements:
In non-seismic design, the stirrup diameter should not be less than 8mm; in seismic design, the stirrup diameter should not be less than 10mm;
In non-seismic design, the stirrup spacing should not be greater than 150mm; in seismic design, the stirrup spacing should not be greater than 100mm along the length of the beam. When cross braces are installed in the beam, the stirrup spacing should not be greater than 150mm;
The diameter of the upper and lower longitudinal steel bars of the frame tube beam should not be less than 16mm, the diameter of the waist bars should not be less than 10mm, and the distance between the waist bars should not be greater than 200mm.
Cross-concealed braces should be used for frame tube beams and inner tube connecting beams with a span-to-height ratio not greater than 2; cross-concealed braces should be used for frame tube beams and inner tube connecting beams with a span-to-height ratio not greater than 1, and should meet the following requirements:
1. The cross-sectional width of the beam should not be less than 300mm;
2 All shear forces should be borne by concealed braces. Each concealed brace should be composed of 4 longitudinal steel bars. The diameter of the longitudinal bars should not be less than 14mm. Its total area As should be calculated according to the following formula:
The longitudinal steel bars for diagonal bracing in both directions should be tied together with rectangular stirrups or spiral stirrups. The stirrup diameter should not be less than 8mm, and the stirrup spacing should not be greater than 200mm and half the beam cross-section width; the stirrups in the end density area should not be less than 8mm. The spacing between ribs should not be greater than 100mm, and the length of the dense area should not be less than 600mm and twice the width of the beam section;
The length of the longitudinal reinforcement extending into the vertical member should not be less than 1a1. In non-seismic design, 1a1 can be taken as 1a; in seismic design, 1a1 should be taken as 1.151a;
The configuration of ordinary stirrups within the beam shall comply with the structural requirements of Article 9.3.7 of this regulation.
Frame-shear wall structure
Frame-shear wall structure composition and stress characteristics
Composition: The frame structure has a large free and flexible use space; the shear wall can provide great lateral stiffness to reduce the lateral displacement of the structure under horizontal action and improve the structure's seismic resistance. Therefore, frame-shear wall structures have a wide range of applications.
Force characteristics
In frame-shear wall structures, the frame and shear walls carry both vertical loads and lateral forces.
Under the action of vertical load, the frame and shear wall respectively bear the vertical force within their load range.
Under the action of lateral forces, the frame and shear walls work together to resist the lateral forces.
Since the deformation characteristics of frames and shear walls are completely different when they bear lateral forces alone, the distribution of lateral forces between frames and shear walls is not only related to the stiffness ratio between the frame and shear walls, but also Varies with altitude.
When the lateral force acts alone on the frame structure, the lateral displacement curve of the structure is shear-shaped, as shown in Figure 15-38(a); when the lateral force acts alone on the hand-shear wall structure, the lateral displacement curve of the structure is curved. , Figure 15-38(b). When lateral forces act on the frame-shear wall structure, it is due to the connection effect of the floor structure. If the overall torsion of the structure does not occur, the frame and shear wall must have the same lateral displacement at each floor. The coordinated lateral displacement curve of the structure is shown in Figure 15-38 (C), which is a bending-shear type.
It can be seen that the influence of the frame and shear wall on the lateral displacement curve of the entire structure changes along the height direction of the structure. At the bottom of the structure, the inter-story displacement of the frame structure is large, and the inter-story displacement of the shear wall structure is small. The shear wall plays a greater role, and the deformation of the frame structure is "constrained" by the shear wall structure; while at the At the top of the structure, the inter-story displacement of the frame structure is small, but the inter-story displacement of the shear wall structure is large. The shear wall is "supported" by the frame structure, as shown in Figure 15-38 (c) and (d). The above-mentioned interaction between the frame and the shear wall is realized with the help of the shear force in the plane of the floor structure. Therefore, in the frame-shear wall structure, the integrity and in-plane stiffness of the floor structure must be guaranteed.
The lateral displacement curve of the frame-shear wall structure is bending-shear type, and the lateral displacement curve of the structure changes with the change of the stiffness characteristic value λ of the frame-shear wall structure. For bending-type lateral displacement curves, the maximum inter-story displacement is at the top layer of the structure; for shear-type lateral displacement curves, the maximum inter-story displacement is at the bottom layer of the structure; for bending-shear type curves, the maximum inter-story displacement is at the middle of the structure .
Number and arrangement of shear walls in frame-shear wall structures
Reasonable number of shear walls
In the frame-shear wall structure, the number of shear walls directly affects the seismic performance of the entire structure and the civil construction cost. With more shear walls arranged, the lateral stiffness of the structure is large and the lateral displacement is small; but the amount of material increases, and at the same time, due to the shortened natural vibration period of the structure, the self-weight of the structure increases, resulting in an increase in the seismic response, that is, the lateral force get bigger. On the contrary, less shear walls are arranged, and the amount of material is reduced. Because the structure is softer, the natural vibration period becomes longer, and the seismic response, that is, the seismic force becomes smaller; but the lateral stiffness of the structure is small, the lateral displacement is large, and the earthquake The rear structure is cracked or severely damaged.
In the expanded preliminary design stage or as a principle of structural design, the layout of shear walls should meet the requirements of the lateral stiffness of the structure. That is, while the apex displacement of the structure and the maximum inter-story displacement of the structure are calculated to meet the high-standard limit values, they should also be checked. Control the natural vibration period of the structure within a reasonable range. It is generally believed that when the basic natural vibration period of the structure T = (0.1~0.15)n (n is the number of structural layers), the number of shear walls and the cross-sectional size of the components are more reasonable.
The layout of shear walls in frame-shear wall structures should meet the following requirements
Shear walls should be evenly arranged near the periphery of the building, in stairwells, elevator rooms, and locations with changes in plane shape and large dead loads. The spacing between shear walls should not be too large;
When the plane shape has large concavities and convexities, it is advisable to arrange shear walls near the ends of the protruding parts;
Longitudinal and transverse shear walls should be formed into L-shaped, T-shaped, [-shaped and other types;
The horizontal shear force borne by the bottom of the single-piece shear wall should not exceed 40% of the total horizontal shear force at the bottom of the structure;
The shear wall should run through the entire height of the building, and sudden changes in stiffness should be avoided; when openings are opened in the shear wall, the openings should be aligned up and down;
Shafts such as buildings and elevator rooms should be arranged in conjunction with nearby lateral force-resistant structures as much as possible;
During seismic design, the shear walls should be arranged so that the lateral stiffness in each main axis direction of the structure is close to each other.
The function and layout of floor structure
The cooperative work of frame and shear wall needs to be ensured by the floor structure. In the frame-shear wall structure, the function of the floor sometimes only transmits horizontal thrust and does not transmit out-of-plane bending moment and shear force, which is equivalent to a hinged rigid connecting rod; sometimes it transmits both horizontal thrust and bending moment, which is equivalent to a connecting rod. beams, which should be determined in the analysis based on the specifics of the structural layout.
First, in order to ensure that the frame and shear walls can jointly withstand lateral forces, the stiffness of the floor structure within its own plane must be guaranteed. Taking the bottom of the structure as an example, since the lateral stiffness of the shear wall is much greater than that of the frame, when they are subjected to the same lateral external force, the lateral displacement of the shear wall is smaller than that of the frame at the same floor. At this time, the floor structure can be regarded as a deep beam supported on two adjacent shear walls, as shown in Figure 15-39. In order to ensure the spatial collaborative performance of the frame and shear wall under the action of lateral forces, the deflection of the horizontal deep beam of the floor should be limited. On the one hand, the structural integrity of the floor itself should be ensured and no openings in the floor should be avoided. For openings that are too large, on the other hand, the spacing between shear walls should be controlled to meet the requirements of Table 15-12. In the table, B is the width of the floor structure.
When the spacing between shear walls is less than the limit value in Table 15-12, the stiffness of the floor structure in its own plane can be regarded as infinite, that is, the floor only undergoes rigid body displacement in the plane after the structure is stressed.
Secondly, the internal force distribution in the frame-shear wall structure is also affected by the out-of-plane stiffness of the floor structure. As shown in Figure 15-40(a)
If the frames and shear walls are not in a straight line, the floor functions as an articulated rigid connecting rod that only transmits horizontal thrust and does not transmit out-of-plane bending moments and shear forces. This type of structural scheme is called a frame-shear wall structural articulated system.
If the shear wall and the frame are located in the same vertical plane and are connected by connecting beams, in addition to the axial force in the connecting beam, the shear force and bending moment in the vertical plane will also be transmitted between the frame and the shear wall. , the shear force will produce axial tension and pressure in the frame column and shear wall respectively, and the resulting bending moment will balance the bending moment generated by part of the external force. This type of structural scheme is called a frame-shear wall structural rigid connection system.
Possible combinations of frame-shear wall structures
The frame and shear wall (single wall, joint wall or smaller shaft) are arranged separately;
Embedding shear walls (framed shear walls) in several spans of the frame structure;
Arrange frames and shear walls continuously and separately within a single piece of lateral force-resisting structure;
A mixture of two or three of the above.
Several issues in the design of frame shear wall structures
For a frame-shear wall structure designed for seismic resistance, when the seismic overturning moment borne by the frame part is greater than 50% of the total seismic overturning moment of the structure under the action of the basic vibration mode earthquake, the seismic grade of the frame part shall be adopted as that of the frame structure, and the column axis The pressure ratio limit should be adopted according to the provisions of the frame structure; the maximum applicable height and aspect ratio limits can be appropriately increased compared to the frame structure.
During seismic design, the total shear force of each layer of the frame of the frame-shear wall structure corresponding to the standard value of earthquake action should meet the following requirements:
For floors that meet the requirements of type (8.1.4), the total frame shear force does not need to be adjusted; for floors that do not meet the requirements of type (8.1.4), the total frame shear force should be based on 0.2V0 and 1.5Vf, max 2 The smaller value shall be used; Vf≥0.2V0
After the total seismic shear force borne by each floor frame is adjusted according to paragraph 1 of this article, the standard values of shear force and end bending moment of each frame column and the frame beam connected to it shall be adjusted according to the ratio of the total shear force before and after adjustment. , the standard value of the axial force of the frame column does not need to be adjusted;
When calculating seismic effects based on the mode decomposition response spectrum method, the adjustments specified in paragraph 1 of this article may be made after the mode combination.
When calculating seismic effects based on the mode decomposition response spectrum method, the adjustments specified in paragraph 1 of this article may be made after the mode combination.
The frame-shear wall structure should be designed as a two-way lateral force-resisting system. During seismic design, shear walls should be arranged in both main axes of the structure.
In the frame-shear wall structure, hinged joints should not be used between the main structural members except for individual nodes; the center lines of beams and columns or columns and shear walls should coincide; when there is a deviation between the center lines of frame beams and columns, they should comply with The relevant provisions of Article 6.1.3 of these regulations.
In buildings with a long rectangular plane or a long part of the plane, the layout of the shear walls should still meet the following requirements:
The spacing of transverse shear walls along the length direction should meet the requirements of Table 8.1.8. When there are large openings in the floor between these shear walls, the spacing of the shear walls should be appropriately reduced;
Longitudinal shear walls should not be concentrated at both ends of the house.
Frame-Shear Wall Structural Calculations
Composition and arrangement of shear wall structures
Structural composition and structural arrangement
Basic form of shear wall
Shear walls generally have I-shaped, L-shaped, T-shaped, [-shaped, Z-shaped and other cross-sectional forms.
Basic characteristics of shear walls
The height of the shear wall is generally the same as the height of the entire house, and its width is determined according to the building layout; relatively speaking, its thickness is very thin, generally only 20 to 30mm.
The lateral stiffness of a shear wall within the plane of the wall is very large, but the stiffness outside the plane of the wall is very small and can generally be ignored.
Shear wall layout requirements
In shear wall structures, shear walls should be arranged in two directions along the main axis or other directions; for shear wall structures designed for earthquake resistance, structural arrangements with walls in only one direction should be avoided. The cross-section of shear wall piers should be simple and regular. The lateral stiffness of the shear wall structure should not be too large.
High-rise building structures should not adopt shear wall structures that are all short-leg shear walls.
Class B high-rise buildings and Class A high-rise buildings with 9-degree seismic resistance design should not adopt shear wall structures with many short-leg shear walls as specified in Article 7.1.2 of this regulation.
The door and window openings of shear walls should be aligned up and down and arranged in rows to form clear wall limbs and connecting beams. It is advisable to avoid openings with wall piers with widely different stiffnesses. In seismic design, staggered-hole walls should not be used for the bottom reinforcement of shear walls with first, second, and third-level seismic resistance levels; superimposed staggered-hole walls should not be used for shear walls with first, second, and third-level seismic resistance levels.
Longer shear walls should be opened with openings and divided into several wall segments with relatively uniform lengths. Weak connecting beams should be used to connect the wall segments. The ratio of the total height of each independent wall segment to its cross-sectional height should not be less than 2. The height of wall pier section should not be greater than 8m.
Shear walls should be arranged continuously from bottom to top to avoid sudden changes in stiffness.
Bending moments out of the plane of the shear wall should be controlled.
When a shear wall limb is connected to a floor beam in an out-of-plane direction, at least one of the following measures should be taken to reduce the adverse impact of the bending moment at the end of the beam on the wall:
A shear wall connected to the beam is set up along the axis of the beam to resist the out-of-plane bending moment of the wall limb;
When it is not possible to set up a shear wall connected to the axis of the beam, buttress columns should be set up at the intersection of the wall and the beam. The cross-section and reinforcement of buttress columns should be determined according to calculations;
When buttress columns cannot be installed, concealed columns should be installed at the intersection of the wall and the beam, and the reinforcement should be determined according to calculations;
If necessary, steel can be installed in the shear wall.
Coupling beams with a span-to-height ratio less than 5 formed by openings in shear walls shall be designed in accordance with the relevant provisions of this chapter. When the span-to-height ratio is not less than 5, they should be designed as frame beams.
In seismic design, generally the height of the reinforced part at the bottom of a shear wall structure can be taken as the greater of 1/8 of the total height of the wall limbs and the two bottom floors. When the height of the shear wall exceeds 150m, the height of the reinforced part at the bottom can be taken as 1/10 of the total height of the wall piers; the height of the reinforced part at the bottom of the partially frame-supported shear wall structure shall comply with the provisions of Article 10.2.4 of this regulation.
It is not appropriate to support the main floor beams on the connecting beams between shear walls.
When floor beams are connected to shear walls, the longitudinal steel bars in the beams should extend into the wall and be reliably anchored.
The shear wall structure should have appropriate lateral stiffness, and its layout should comply with the following regulations
The plane layout should be simple and regular, and should be arranged bidirectionally along the two main axes or other directions. The lateral stiffness in the two directions should not differ too much. When designing for earthquake resistance, structural arrangements with walls in only one direction should not be adopted.
It should be arranged continuously from bottom to top to avoid sudden changes in stiffness.
Door and window openings should be aligned up and down and arranged in rows to form clear wall limbs and connecting beams; openings that cause wide differences in the width of wall limbs should be avoided; during seismic design, the bottom reinforcement parts of first-, second-, and third-level shear walls should not be used If the upper and lower openings are not aligned with each other, it is not appropriate to use a superimposed staggered wall with partially overlapping openings throughout the entire height.
The concrete strength grade of shear wall structures should not be lower than C20; the concrete strength grade of shear wall structures with barrel and short-leg shear walls should not be lower than C25.
Section thickness regulations for shear walls
It should comply with the wall stability verification requirements in Appendix D of the high-tech regulations.
Secondary shear wall: the reinforced part at the bottom should not be less than 200mm, and other parts should not be less than 160mm; the reinforced part at the bottom of a straight-line independent shear wall should not be less than 220mm, and other parts should not be less than 180mm.
Level 3 and 4 shear walls: should not be less than 160mm, and the bottom reinforced part of the straight-shaped independent shear wall should not be less than 180mm.
In non-seismic design, it should not be less than 160mm.
In shear wall shafts, the section thickness of the wall limbs that separate the elevator shaft or pipe shaft can be appropriately reduced, but should not be less than 160mm.
Layout requirements for short leg shear walls
High-rise building structures should not adopt shear wall structures that are all short-leg shear walls. When there are many short-limb shear walls, the cylinder (or general shear wall) should be arranged to form a shear wall structure in which the short-limb shear wall and the cylinder (or general shear wall) jointly resist horizontal force, and should comply with the following Regulation:
Its maximum applicable height should be appropriately lower than the specified value for shear wall structures in Table 4.2.2-1 of the height regulation, and the 7-degree and 8-degree seismic design should not be greater than 100m and 60m respectively;
During seismic design, the bottom overturning moment of the first mode of vibration experienced by a general shear wall should not be less than 50% of the total seismic overturning moment at the bottom of the structure; the bottom overturning moment of the short-leg shear wall should not be greater than 50% of the total seismic overturning moment at the bottom of the structure. %;
During seismic design, the seismic resistance grade of the short-leg shear wall should be one level higher than the seismic grade of the shear wall specified in Table 4.8.2 of this regulation;
During the seismic design, the axial pressure ratio of the axial force design value generated by the short-leg shear wall at each layer under the action of the representative value of the gravity load should not be greater than 0.5, 0.6 and 0.7 respectively when the seismic grade is one, two and three; for wingless For straight-shaped short-leg shear walls with edge or end columns, the axial compression ratio limit shall be reduced by 0.1 accordingly;
During the seismic design, except for the bottom reinforced part, which should be adjusted according to Article 7.2.10 of this regulation, the shear design values of the short-limb shear walls on other floors should be multiplied by the first and second seismic grades respectively. Coefficients 1.4 and 1.2.
During seismic design, the reinforcement ratio of all longitudinal steel bars in the short-leg shear wall section should not be less than 1.2% at the bottom reinforcement part and not less than 1.0% at other parts;
The section thickness of short-leg shear wall should not be less than 200mm;
In 7-degree and 8-degree seismic design, flanges should be provided for short-leg shear walls. It is not appropriate to arrange floor beams that intersect with one side of the straight-shaped short-leg shear wall outside the plane.
Note: Short-leg shear wall refers to a shear wall with a cross-section thickness of not more than 300 mm and a ratio of wall limb cross-section height to thickness of 5 to 8; general shear wall refers to a shear wall with a ratio of wall limb cross-section height to thickness greater than 8. force wall.
For the structural layout requirements of the large space shear wall at the bottom, see the structural layout requirements of high-rise buildings with transfer floors in complex high-rise buildings.
Several issues in calculation of shear wall structures
Composition and arrangement of multi-layer frame structures
The composition of the frame structure
Made up of beams and columns connected.
The frame nodes at the intersection of beams and columns are usually rigidly connected, and sometimes some nodes are also made into hinged or semi-articulated joints.
The bottom of the column is generally a fixed support, and if necessary, it is also designed as a hinge support.
In order to facilitate the stress bearing of the structure, the frame beams should be straightened and aligned, the frame columns should be aligned vertically and horizontally, and centered up and down, and the axes of the beams and columns should be in the same vertical plane.
Sometimes due to functional or architectural requirements, the frame structure can also be made with missing beams retracted or beams arranged diagonally, as shown in Figure 14-1.
Infill walls in frame structures
Rigid infill walls in frame structures can make the structure stiffer
The frame structure is a high-order statically indeterminate structure that bears both vertical loads and lateral forces, such as wind loads or horizontal earthquakes. Generally speaking, the effect of the infill wall on the frame side resistance is not considered in the calculation, because the existence of the infill wall is uncertain during the use of the building, and the infill wall is often made of lightweight materials, or between columns and walls. Leave gaps only for flexible connections via steel bars. However, when the infill wall is a masonry wall and is rigidly connected to the frame structure, for example, the upper part of the masonry infill wall and the bottom of the frame beam are fully "plugged", or when the construction sequence of building the wall first and then pouring the beam is adopted, then Under horizontal earthquake action, the frame structure will undergo lateral deformation and the infill wall will act as a baroclinic bar. As shown in Figure 14-2. Under the action of horizontal earthquakes, rigid infill walls make a greater contribution to the lateral stiffness of the frame. Care should be taken to make the overall lateral stiffness of the structure symmetrical as much as possible to avoid excessive overall torsion during earthquakes.
Types of frame structures
The cast-in-place frame, that is, the beams, columns, and floors are all cast-in-place reinforced concrete structures.
Prefabricated frame refers to a frame structure in which beams, columns, and floors are all prefabricated and assembled and connected through welding.
The integrated frame means that the beams, columns, and floors are all prefabricated. After the components are hoisted into place, the steel bars in the node areas are welded or tied, and the concrete in the node areas is poured, thereby connecting the beams, columns, and floors into an integral frame structure.
Frame structure layout
Column grid layout
The layout of the column grid should meet the requirements of the production process (inner corridor type, equal span type, symmetrical unequal span type)
The column grid layout should meet the requirements of the building layout (hotel, office building)
The column grid layout should ensure that the structural stress is reasonable
The layout of the column grid should be convenient for construction
Layout of load-bearing frames
Transverse frame load-bearing plan
Longitudinal frame load-bearing plan
Mixed load-bearing scheme of vertical and horizontal frames
The basis of multi-layer frame structures
Foundation embedment depth: generally refers to the distance from the bottom of the foundation to the outdoor design ground, referred to as foundation embedment depth. When a box foundation or raft foundation is used in the basement, the foundation embedding depth is calculated from the outdoor ground elevation. When using an independent foundation or strip foundation, the calculation should be made from the indoor ground elevation.
Generally, there are independent foundations under columns, strip foundations, cross foundations, and sheet pile foundations. Box foundations or pile foundations can also be used when necessary.
The strip foundation is arranged in a strip shape, and the cross section is generally in the shape of an inverted T. Its function is to transfer the load of the upper structure from each column to the foundation more evenly, and at the same time, it connects the upper frame structures into a whole to increase the The integrity of the structure reduces uneven settlement. The strip foundation can be arranged longitudinally or transversely.
The cross-shaped foundation is arranged in a cross shape, that is, strip foundations are arranged along the vertical and horizontal directions of the column network, which not only expands the load-bearing area of the base, but also allows the superstructure to be connected in both vertical and horizontal directions, and has strong overall spatial stiffness.
If the bottom area of the cross-shaped foundation cannot meet the requirements for the bearing capacity of the foundation and the allowable deformation of the superstructure, the bottom area of the foundation can be expanded until the bottom plates are connected into one piece, which becomes a raft foundation. The raft foundation can be made into flat plate or beam plate type. The flat-plate raft foundation is actually a flat plate of equal thickness, and the construction is simple and convenient, but the amount of concrete is large; the beam-slab raft foundation generally arranges ribs along the column network in the vertical and horizontal directions, which can reduce the thickness of the bottom plate and enhance the structural stiffness, but The construction is more complicated.
The choice of foundation type depends on factors such as the on-site engineering geological conditions, the size of the superstructure load, the sensitivity of the superstructure to uneven settlement and tilt of the foundation soil, and construction conditions. Necessary technical and economic comparisons should be made during design and determined after comprehensive consideration.
Principles for determining foundation burial depth: On the premise of meeting foundation stability and deformation requirements and related requirements, the foundation should be buried as shallowly as possible.
What factors should be considered when determining the depth of foundation embedding?
The purpose of the building, whether there is a basement, equipment foundation and underground facilities, the form and construction of the foundation.
The magnitude and nature of the loads acting on the foundation.
Engineering geology and hydrogeological conditions.
The depth of foundations of adjacent buildings.
Effects of frost heaving and melting subsidence of foundation soil.
Frame structure height calculation
The floor height of the frame, that is, the length of the frame columns, can be taken as the corresponding building floor height, that is, the height from the current floor to the upper floor, but the floor height of the bottom floor should be taken as the distance from the top surface of the foundation to the top surface of the second floor. .
high-rise building
Overview
Definition and height calculation of high-rise buildings
Definition: In my country's "Technical Regulations for Concrete Structures of High-Rise Buildings" (hereinafter referred to as "High-rise Regulations"), it is stipulated that high-rise civil buildings with concrete structures of 10 floors and above or the height of the building exceeds 28m are called high-rise buildings, and conventional height The high-rise buildings are called Class A high-rise buildings, and the high-rise buildings whose height exceeds the Class A height limit are called Class B high-rise buildings. (High-rise residential buildings with concrete structures of ten floors or more or with a building height exceeding 28 meters or public buildings with a height exceeding 24 meters are called high-rise buildings. High-rise buildings with regular heights are called high-rise buildings with a height of Class A, and those with a height exceeding Class A are called high-rise buildings. The high-rise buildings with the height limit are called B-height high-rise buildings).
Height calculation:
The maximum applicable height of Class A reinforced concrete high-rise buildings is shown in Table 15-1. The maximum applicable height of Class B reinforced concrete high-rise buildings is shown in Table 15-2. For Class A buildings, the above two tables should be checked and used after the fortification intensity is increased by one degree. , for buildings located in Category IV sites or irregular special buildings, the applicable height should be appropriately reduced.
In structural design, the height of a high-rise building generally refers to the distance from the outdoor ground to the main roof, excluding the height of water tanks, elevator rooms, basements, etc. that protrude from the roof.
Stress characteristics of high-rise building structures
In high-rise building structures, under the action of vertical loads, the axial force in the column increases with the increase in the number of floors. It can be approximately considered that the axial force has a linear relationship with the number of floors, see Figure 15-l(a);
The horizontal wind load or earthquake force can be approximately considered to be distributed in a triangle or an inverted triangle. The bending moment generated by this distributed force at the bottom of the structure is proportional to the cubic height of the structure, see Figure 15-1 (b) ,
The lateral displacement of the structure's vertex under the action of horizontal force is proportional to the fourth power of the height, see Figure 15-1(c). The above-mentioned bending moments and lateral displacements often become the controlling factors that determine the structural plan, structural layout and component section size.
Advantages and disadvantages of high-rise buildings
Advantages: High-rise buildings can bring obvious socio-economic benefits: first, they concentrate the population, and the vertical and horizontal traffic inside the building can be used to shorten the contact distance between departments, thus improving efficiency; second, they can make the land used for large-area buildings larger The scope is reduced, and it is possible to select a site in the center of the city; third, it can reduce municipal construction investment and shorten the construction period. Fourth, high-rise buildings have better ventilation and higher air quality in areas away from the ground. Finally, high-rise buildings are also a symbol of a city's development level.
Disadvantages: ① Regarding urban economic and environmental benefits, construction should be based on the location and control height designated by the urban planning department, and cannot be completely based on the needs of the building itself. ② Due to the increased stress of high-rise buildings, the level of equipment and decoration must be improved, and the construction difficulty increases, so the cost must be much higher than that of multi-story buildings. Therefore, designers from all walks of life need to work closely together to make the floor plan reasonable, improve the utilization factor, achieve a simple structure, light weight, easy installation, and comprehensively reduce the cost. ③The most prominent thing about high-rise buildings is fire safety design. Designers from all industries should strictly abide by the regulations on fire protection design of high-rise buildings. Fire problems in high-rise buildings are often mentioned in the news, which shows that its fire safety design is relatively difficult.
Limitation of horizontal displacement of high-rise building structures
Under normal conditions of use, high-rise buildings should be in an elastic state and have sufficient stiffness. To this end, the "High-rise Regulations" stipulate the ratio of the maximum displacement between floors to the floor height Δu/h as follows.
a. For high-rise buildings with a height of no more than 150m, the ratio Δu/h of the maximum floor-to-floor displacement to floor height should not be greater than the limit in Table 15-3.
b. For high-rise buildings with a height equal to or greater than 250m, the ratio of the maximum floor-to-floor displacement to floor height △u/h should not be greater than 1/500;
c. 3 For high-rise buildings with a height between 150 and 250m, the limit value of the ratio of the maximum displacement between floors to the floor height △u/h shall be linearly interpolated from the limits in paragraphs 1 and 2 of this article.
Note: The maximum displacement △u between floors is calculated based on the maximum horizontal displacement difference of the floor, without deducting the overall bending deformation. During seismic design, the calculation of floor displacements specified in this article does not take into account the influence of accidental eccentricity.
General provisions for structural design of high-rise buildings
High-rise buildings should not adopt seriously irregular structural systems and should meet the following requirements:
(1) It should have the necessary bearing capacity, stiffness and deformation capacity;
(2) It should be avoided that the entire structure loses its ability to withstand gravity load, wind load and earthquake action due to damage to part of the structure or components;
(3) Effective measures should be taken to strengthen possible weak areas.
(4) The vertical and horizontal layout of the structure should have reasonable stiffness and bearing capacity distribution to avoid weak spots caused by local mutation and torsion effects;
(5) It is advisable to have multiple anti-seismic defense lines.
(6) In addition to complying with the above regulations, the design of complex high-rise building structures and hybrid structures should also comply with relevant regulations on the design of complex high-rise building structures and hybrid structures.
Vertical and horizontal structural systems of high-rise building structures
The vertical structural systems of reinforced concrete high-rise buildings include:
frame structure system
shear wall structural system
frame-shear wall structural system
Cylinder structure system, etc.
Horizontal structure refers to floor and roof structures
In high-rise buildings, the main role of horizontal structures
Bear vertical loads acting on floors or roofs
Connect all vertical load-bearing components.
Transmit or distribute horizontal forces to vertical structural members
Floor plan requirements for high-rise building structures
In an independent structural unit of a high-rise building, the structure plane shape should be simple and regular, and the stiffness and bearing capacity should be evenly distributed. Severely irregular floor plans should not be used.
High-rise buildings should choose a plan shape with less wind effect.
For grade A reinforced concrete high-rise buildings designed for earthquake resistance, the layout should meet the following requirements:
a. The plane should be simple, regular, and symmetrical to reduce eccentricity;
b. The plane length should not be too long, and the length l of the protruding part should not be too large (height gauge figure 4.3.3); the values of L and l should meet the requirements of Table 4.3.3;
c. It is not suitable to use plane graphics with overlapping corners or thin waist-shaped plane graphics.
For seismic-resistant grade B reinforced concrete high-rise buildings, mixed-structure high-rise buildings and complex high-rise buildings referred to in high-rise buildings, the layout should be simple and regular to reduce eccentricity.
The structural floor plan should be designed to reduce the effects of torsion.
When the floor plane is relatively long and narrow, and there are large recesses and openings that cause the floor to be greatly weakened, the adverse effects of floor weakening should be considered in the design.
For buildings with large extension lengths such as L-shaped and tic-shaped buildings, when the central part of the building and the elevator room greatly weaken the floor, the structural measures of the floor and the connecting wall should be strengthened, and if necessary, grooves in the extended section should be strengthened. Install connecting beams or connecting plates.
After the large hole in the floor is weakened, the following structural measures should be taken to strengthen it:
1 Thicken the floor near the opening to increase the reinforcement ratio of the floor; use double-layer two-way reinforcement or add diagonal steel bars;
2 Set side beams and concealed beams at the edge of the opening;
3 Concentrate diagonal steel bars at the corners of floor openings.
During seismic design, high-rise buildings should adjust their plane shape and structural layout to avoid irregular structures and no seismic joints. When the building's plane shape is complex and its plane shape and structural layout cannot be adjusted to make it a more regular structure, it is appropriate to set up earthquake-proof joints to divide it into several simpler structural units.
When setting up anti-seismic joints, the relevant regulations of high standards should be complied with.
Vertical layout requirements for high-rise building structures
(1) The vertical shape of high-rise buildings should be regular and uniform, and excessive overhangs and inwards should be avoided. The lateral stiffness of the structure should be larger at the bottom and smaller at the top, and change gradually and evenly. Structures with severely irregular vertical layout should not be used.
(2) For high-rise building structures designed for earthquake resistance, the lateral stiffness of floors should not be less than 70% of the lateral stiffness of the adjacent upper floor or 80% of the average lateral stiffness of the three adjacent floors above it.
(3) The shear bearing capacity of the lateral force-resistant structure between floors of a Grade A high-rise building should not be less than 80% of the shear bearing capacity of the upper floor, and should not be less than 65% of the shear bearing capacity of the upper floor; The shear bearing capacity of the lateral force-resistant structure between floors of a Class B high-rise building shall not be less than 75% of the shear bearing capacity of the floor above it.
Note: The shear bearing capacity of the lateral force-resistant structure between floors refers to the sum of the shear bearing capacity of all columns and shear walls of the floor in the direction of horizontal earthquake action considered.
(4) During seismic design, the vertical lateral force-resisting members of the structure should be continuous from top to bottom.
(5) During seismic design, when the ratio of the height H1 of the retracted part of the upper floor of the structure to the outdoor ground and the height H of the house is greater than 0.2, the retracted horizontal dimension B1 of the upper floor should not be less than 0.75 times the horizontal dimension B of the lower floor ( Height Plan 4.4.5a, b); when the upper structure floor overhangs relative to the lower floor, the horizontal dimension B of the lower floor should not be less than 0.9 times the horizontal dimension B1 of the upper floor, and the horizontal overhang dimension a should not be greater than 4m (high Figure 4.4.5c, d).
(6) When some walls and columns are removed from the top floor of the structure to form an open room, elastic dynamic time history analysis and calculation should be carried out and effective structural measures should be taken.
(7) High-rise buildings should have basements.
role in high-rise buildings
vertical load
(1) The floor live load of high-rise building structures should be adopted in accordance with the relevant provisions of the current national standard "Code for Loading of Building Structures" GB50009.
(2) When using wall-attached towers, climbing towers and other lifting machinery or other construction equipment that have an impact on the structural stress during construction, the impact of the construction load on the structure should be checked based on the specific circumstances.
(3) The dead weight of the revolving restaurant track and driving equipment should be determined according to the actual situation.
(4) The size and position of cleaning equipment such as window cleaning machines should be determined according to their actual conditions.
(5) The live load of the helicopter platform should be the load that can produce the maximum internal force on the platform from the following two types:
wind load
Basic wind pressure: The benchmark pressure of wind load, generally based on the 10min average wind speed observation data at a height of 10m on the local open flat ground. Through probability statistics, the wind speed determined by the maximum value once in 50 years is obtained, and then the corresponding air density is considered. The wind pressure determined by formula ( ).
When calculating the main structure, the standard value of the wind load perpendicular to the building surface should be calculated according to the following formula, and the wind load action area should be the maximum projected area perpendicular to the wind direction.
The basic wind pressure should be adopted in accordance with the current national standard "Code for Loading of Building Structures" GB 50009. For high-rise buildings that are particularly important or sensitive to wind loads, the basic wind pressure should be based on the wind pressure value with a 100-year return period.
For high-rise buildings located on flat or slightly undulating terrain, the wind pressure height variation coefficient should be determined according to Table 3.2.3 of the height regulation according to the ground roughness category. Ground roughness should be divided into four categories: Category A refers to offshore sea surfaces and islands, coasts, lakeshores and desert areas; Category B refers to fields, villages, jungles, hills, towns and urban suburbs with sparse houses; Category C refers to dense buildings Category D refers to urban areas with dense building groups and taller houses.
For high-rise buildings located in mountainous areas, after determining the wind pressure height change coefficient according to Article 3.2.3 of the High-rise Regulations, it should be revised according to the relevant provisions of the current national standard "Load Code for Building Structures" GB 50009.
When calculating the wind load effect of the main structure, the wind load type coefficient μs can be used according to the following regulations:
For circular plan buildings, take 0.8;
Regular polygonal and truncated triangle planar buildings are calculated by the following formula:
For rectangular, square, and cross-shaped buildings with a height-to-width ratio H/B not greater than 4, take 1.3;
Take 1.4 for the following buildings:
V-shaped, Y-shaped, arc-shaped, double cross-shaped, and tic-shaped plan buildings;
L-shaped, trough-shaped and cross-shaped plan buildings with a height-to-width ratio H/B greater than 4;
Rectangular and drum-shaped plan buildings with a height-to-width ratio H/B greater than 4 and a length-width ratio L/B not greater than 1.5.
In situations where more detailed wind load calculations are required, the wind load type coefficient can be adopted in accordance with Appendix A of the high-level regulations, or determined by wind tunnel testing.
The wind vibration coefficient βz of high-rise buildings can be calculated as follows:
When multiple or clustered high-rise buildings are close to each other, the group effect of mutual wind interference should be considered.
When the height of the house is greater than 200m, a wind tunnel test should be used to determine the wind load of the building; when the height of the house is greater than 150m and one of the following conditions occurs, a wind tunnel test should be used to determine the wind load of the building:
The plane shape is irregular and the facade shape is complex;
Facade openings or conjoined buildings;
The surrounding terrain and environment are complex.
For horizontal components such as cornices, awnings, sunshades, and balconies, when calculating local floating wind loads, the wind load type coefficient μs should not be less than 2.0.
When designing building curtain walls, wind loads should be adopted in accordance with the current national design standards for building curtain walls.
earthquake effect
The calculation of seismic effects of high-rise buildings of various seismic fortification categories should comply with the following regulations:
Category A buildings: The seismic fortification intensity should be higher than that of the local area, and its value should be determined based on the approved seismic safety evaluation results;
Category B and C buildings: should be calculated according to the seismic fortification intensity of the region.
High-rise building structures should consider earthquake effects according to the following principles:
Generally speaking, the calculation of horizontal seismic effects should be considered separately in the two main axes of the structure; for structures with oblique lateral force-resisting members, when the intersection angle is greater than 15°, the horizontal seismic effects in the directions of each lateral force-resisting member should be calculated separately ;
For structures with obviously asymmetric and uneven distribution of mass and stiffness, the torsional effects under two-way horizontal earthquakes should be calculated; in other cases, the torsional effects under one-way horizontal earthquakes should be calculated;
When designing for 8-degree and 9-degree seismic resistance, vertical seismic effects should be considered for long-span and long cantilever structures in high-rise buildings;
Vertical seismic effects should be calculated during 9-degree seismic design.
The influence of accidental eccentricity should be considered when calculating unidirectional seismic effects. The offset value of the centroid of each layer along the direction perpendicular to the earthquake action can be used as follows:
High-rise building structures should adopt the following calculation methods according to different situations:
a. High-rise building structures should adopt the mode decomposition response spectrum method. For structures with asymmetric and uneven mass and stiffness, as well as high-rise building structures with a height exceeding 100m, the mode decomposition response spectrum method that considers the influence of torsional coupling vibration should be used;
b. For high-rise building structures with a height not exceeding 40m, where shear deformation is the main factor, and the mass and stiffness are relatively evenly distributed along the height, the bottom shear method can be used;
c. For high-rise buildings with 7-9 degree seismic fortification, the elastic time history analysis method should be used for supplementary calculations under frequent earthquakes in the following situations:
Category A high-rise building structures;
Category B and C high-rise building structures listed in Table 3.3.4 of the high-level regulations;
High-rise building structures that do not meet the requirements of Articles 4.4.2 to 4.4.5 of the regulations;
Complex high-rise building structures specified in Chapter 10 of these regulations;
High-rise building structures with particularly uneven distribution of mass along the vertical direction.
When conducting dynamic time history analysis according to high-level regulations, the following requirements should be met:
a. No less than two sets of actual earthquake records and one set of artificially simulated acceleration time history curves should be selected according to the type of building site and the design earthquake grouping. The average seismic influence coefficient curve should be consistent with the seismic influence used by the mode decomposition response spectrum method. The coefficient curves are consistent in a statistical sense, and during elastic time history analysis, the structural bottom shear calculated from each time history curve should not be less than 65% of the bottom shear calculated by the mode decomposition response spectrum method. Multiple time histories The average value of the bottom shear force of the structure calculated by the curve should not be less than 80% of the bottom shear force calculated by the mode decomposition response spectrum method.
b. The duration of seismic waves should not be less than 3 to 4 times the basic natural vibration period of the building structure, nor should it be less than 12s. The time interval of seismic waves can be 0.01s or 0.02s;
c. Enter the maximum value of earthquake acceleration, which can be used according to Table 3.3.5;
d. The structural seismic action effect can be the larger value of the average value of the calculation results of multiple time history curves and the calculation results of the mode decomposition response spectrum method.
When calculating earthquake effects, the representative value of the gravity load of the building structure should be the sum of the standard value of the permanent load and the combined value of the variable load. The combination value coefficient of variable load should be adopted according to the following provisions:
The snow load is taken as 0.5;
When calculating the floor live load based on actual conditions, it is taken to be 1.0; when calculated based on the equivalent uniformly distributed live load, it is taken to be 0.8 for libraries, archives and warehouses, and 0.5 for general civil buildings.
When the vertical seismic action is taken into account for long horizontal cantilever members, long-span structures and the overhanging parts of the upper floors of the structure, the standard values of the vertical seismic action can be represented by the gravity load borne by the structure or component respectively when the fortification is at 8 degrees and 9 degrees. 10% and 20% of the value.
The natural vibration period of the structure used to calculate the seismic influence coefficient of each vibration mode should be reduced by considering the stiffness effect of non-load-bearing walls.
Calculation of horizontal and vertical seismic effects
temperature effect
There are three main types of temperature changes that cause internal temperature forces in high-rise building structures, namely: indoor and outdoor temperature differences, sunlight temperature differences and seasonal temperature differences.
Generally speaking. The restraining force within a structure due to temperature changes is proportional to the number of floors within the structure. Structural deformations caused by temperature changes generally include the following:
1. Column bending: Due to the temperature difference between indoor and outdoor, one side of the outer column expands or the other side contracts, and the uneven strain in the column section causes bending.
2. The difference in expansion and contraction between the inner and outer columns: The outer column array is affected by the outdoor temperature, and the inner column array is controlled by the indoor air conditioning temperature. The axial expansion and contraction of the two are inconsistent, which causes out-of-plane shear deformation of the floor structure.
3. Difference in expansion and contraction between the roof structure and the lower floor structure: The exposed roof structure undergoes greater thermal expansion and contraction due to the influence of seasonal sunlight, while the temperature change of the lower floor structure is smaller. Due to the uneven expansion and contraction of the horizontal components of the upper and lower floors, It will cause shear deformation and shear cracks in the wall.
Generally speaking, for buildings with less than 10 floors and when the building plane length is less than 6Om, the effect of temperature change can be ignored. For buildings with 10 to 30 floors, the deformation caused by temperature differences gradually increases. The size of the temperature effect mainly depends on the degree of structural exposure, the stiffness of the floor structure and the height of the structure. As long as appropriate processing is done in the building insulation structure and structural reinforcement structure, the effect of temperature can still be ignored in the calculation of internal forces. For super high-rise buildings with more than 30 floors or more than 10Om, the temperature effect must be paid attention to in the design to prevent structural and non-structural damage to the building.
At present, in our country, there are no specific regulations on how to consider the effect of temperature in the structural design of high-rise buildings. Accurate and practical internal force calculation methods and specific and effective structural measures need to be further studied.
high-rise building foundation
The foundation design of high-rise buildings should comprehensively consider factors such as the engineering geology and hydrogeological conditions of the building site, the type of superstructure and the height of the house, construction technology and economic conditions, so that the building will not suffer excessive settlement or tilt and meet the normal use of the building. requirements; the location and elevation of adjacent underground structures and various underground facilities should also be understood to reduce interaction with adjacent buildings.
In earthquake areas, high-rise buildings should avoid areas that are unfavorable for earthquake resistance; when conditions do not allow avoiding unfavorable areas, reliable measures should be taken to prevent the building from being damaged due to foundation failure or excessive sinking or tilting during an earthquake. .
The foundation design should adopt local mature and reliable technology; the influence of the interaction between the foundation and the superstructure should be considered. If it is necessary to lower the groundwater level during construction, effective measures should be taken to avoid affecting the safety and normal use of adjacent buildings, structures, underground facilities, etc.; at the same time, attention should also be paid to the time requirements for construction precipitation to avoid premature rise in water level after stopping precipitation and causing building Problems such as floating objects.
High-rise buildings should adopt a foundation form that has good integrity, can meet the foundation bearing capacity and allowable deformation requirements of the building, and can adjust uneven settlements; it is advisable to use raft foundations or raft foundations with pile foundations, and box foundations can be used when necessary. . When the geological conditions are good and the foundation bearing capacity and deformation requirements can be met, cross-beam foundations or other forms of foundations can also be used; when the foundation bearing capacity or deformation does not meet the design requirements, pile foundations or composite foundations can be used.
Deformation joint settings
Principles for setting deformation joints (how to avoid or reduce the number of deformation joints)
During architectural design, measures such as adjusting the plane shape, size, and body shape should be adopted;
During structural design, measures such as selecting node connection methods, configuring structural steel bars, and setting rigid layers should be taken;
In terms of construction, measures such as staged construction, post-casting tapes, and thermal insulation layers should be adopted to prevent damage to structural or non-structural components caused by factors such as temperature changes, uneven settlement, and earthquake effects.
When the building plane is long and narrow, or the shape is complex and asymmetrical, or the stiffness, height, and weight of each part vary greatly and the above measures cannot be solved, it is also necessary to set expansion joints, settlement joints, and earthquake-proof joints.
expansion joint
The setting of expansion joints is mainly related to the length of the structure. The "Concrete Code" stipulates the maximum spacing of expansion joints in reinforced concrete structures. For details, see Appendix 9, Maximum Spacing of Expansion Joints in Reinforced Concrete Structures. When the length of the structure exceeds the allowable value specified in the specification, the temperature stress should be calculated and corresponding structural measures should be taken.
Under what circumstances should the spacing of expansion joints be appropriately reduced?
A rack structure with a column height (measured from the top surface of the foundation) less than 8m;
The roof has a rack structure without heat preservation and insulation measures;
Structures located in dry climate areas, areas with hot summers and frequent heavy rains, or structures that are often exposed to high temperatures;
Various wall structures constructed using slip form technology;
The concrete material shrinks greatly and is exposed for a long time during the construction period.
Under what circumstances can the spacing of expansion joints be appropriately increased?
Take measures to reduce concrete shrinkage or temperature changes;
Adopt special prestressing or additional structural steel measures;
Low-shrinkage concrete materials are used, and construction methods such as skip pouring, post-casting tape, and control joints are adopted, and maintenance construction is strengthened.
The spacing between expansion joints of cast-in-place overhangs, rain covers and other exposed structures should not be greater than 12m.
The width of expansion joints and settlement joints should generally not be less than 50mm.
settlement joint
The setting of settlement joints is mainly related to the upper load on the foundation and the geological conditions of the site. When the upper load difference is large, or the physical and mechanical indicators of the foundation soil are very different, settlement joints should be set up. The settlement joints can be made by using cantilever beams or placing prefabricated panels or prefabricated beams, as shown in Figure 14-9.
Shockproof seams
The setting of anti-seismic joints is mainly related to factors such as the plane shape of the building, height difference, stiffness, mass distribution and other factors.
The setting of seismic joints should make each structural unit simple and regular, with uniform stiffness and mass distribution to avoid torsional effects under earthquake action. In order to prevent the structures between the units from colliding with each other when an earthquake occurs, the width of the anti-seismic joints shall not be less than 100mm.
When setting up anti-seismic joints, the following regulations should be met:
The minimum width of anti-seismic joints should meet the following requirements:
For frame structure houses, the height of the part not exceeding 15m can be 100mm; the part exceeding 15m should be widened by 20mm for every additional height of 5m, 4m, 3m and 2m at 6 degrees, 7 degrees, 8 degrees and 9 degrees;
Frame-shear wall structure houses should not be smaller than 1) of this paragraph, and can be adopted at 70% of the value specified in the first item. Shear wall structure houses should not be smaller than 1) of this paragraph, and can be adopted at 50% of the value specified in item 1. However, both should not be less than 100mm.
50% of the value is used, but neither should be less than 100mm. 2 When the structural systems on both sides of the anti-seismic joint are different, the width of the anti-seismic joint should be determined according to the unfavorable structural type;
When the heights of the houses on both sides of the earthquake-proof joint are different, the width of the earthquake-proof joint should be determined according to the lower height of the house;
8. For a frame structure house with a 9-degree seismic design, when the structural heights on both sides of the seismic joint are quite different, the stirrups of the frame columns on both sides of the seismic joint should be densely packed along the full height of the house, and can be placed on both sides of the joint along the full height of the house as needed. Set up no less than two seismic walls perpendicular to the seismic joints;
When there is a large settlement difference between the foundations of adjacent structures, the width of the anti-seismic joints should be increased;
Seismic joints are set along the entire height of the house. There are no seismic joints in the basement and foundation, but the structure and connection are strengthened at the corresponding places with the upper seismic joints;
It is not advisable to use corbel joists to set earthquake-proof joints between structural units or between the main building and the podium. Otherwise, reliable measures should be taken.
Conceptual design of high-rise building structures
Overview of the development of high-rise buildings at home and abroad
The development of high-rise buildings in China
Ancient
modern times
The development of high-rise buildings abroad
Characteristics of high-rise buildings
Classification of high-rise buildings
Category 1: 9~16 floors, height not exceeding 50m
Category 2: 17~25 floors, height not exceeding 75m
Category III: 26~40 floors, height not exceeding 100m
Category III: 26~40 floors, height not exceeding 100m
my country’s definition of high-rise buildings
Characteristics of high-rise buildings
Types of high-rise building structures
steel structure
Advantages: high strength, high toughness, good seismic resistance, easy to process, can shorten the on-site construction period, and is convenient for construction.
Disadvantages: A large amount of steel is used, the cost is high, and the fire resistance is poor.
reinforced-concrete structure
Advantages: low cost, rich sources of materials, can be cast into various complex cross-sectional shapes, and can be composed of various structural systems; can save steel, has high load-bearing capacity, and can obtain better seismic performance after reasonable design.
Disadvantages: The component section is large, it occupies a large area, and it is heavy.
Composite Structure
Advantages: Based on the reinforced concrete structure, it fully utilizes the excellent tensile properties of the steel structure and the compressive properties of the concrete structure to further reduce the weight of the structure and improve the ductility of the structure.
type
Steel reinforced concrete components, steel reinforced concrete components, steel tube reinforced concrete components
Part of the lateral force-resistant structure is made of steel structure, and the other part is made of reinforced concrete structure (or part of it is made of steel frame reinforced concrete structure)
Structural system of high-rise building structures
Basic lateral force resisting unit for high-rise buildings
frame
shear wall
cylinder
Structural system: The way a structure is composed of component units to resist external effects.
Structural system type
Frame structure system: The structure composed of beams and column members connected through nodes is called a frame. The frame structure is the main structural form of multi-story houses and the basic structural unit of high-rise buildings.
frame structure system
pure frame structure
shear wall structural system
Frame-shear wall structural system
Tube-in-tube structural system
multi-tube system
megastructure system